Fluke T6-1000/EU Electrical Tester with FieldSenseâ„¢


request for quote

Description

Product overview: Fluke T6-1000 Electrical Tester

Measure voltage without test leads

The Fluke T6-1000 Electrical Tester with FieldSenseâ„¢ technology lets you quickly, safely take True rms voltage and current measurements without test leads.

Unlike other fork testers that merely detect voltage, the T6-1000 makes actual measurements, without contacting a live, metallic conductor. Just slide the 17.8 mm open fork, the widest in the industry, over a conductor and read simultaneous voltage and current values. Or simultaneous frequency and current values. The open fork works with wires up to AWG 4/0 (120 mm2). Or, you can use the attached test leads to measure voltage DC to 1000 V.

  • True rms voltage and current to 200 A AC, 1000 V AC
  • Resistance 1 Ω to 100 kΩ

Work on any jobsite

Make use of the HOLD button to temporarily freeze the reading on the screen so you can keep working with the same measurement up. Plus, the display features large, easy-to-read numbers and a backlight for darker work environments or inside cabinets. The T6-1000 works with the Fluke TPACK ToolPakâ„¢ Magnetic Meter Hanger to make it even more convenient.

How FieldSenseâ„¢ technology works

FieldSense ™ technology is different than other open fork testers work by interpreting a magnetic field to show AC current. FieldSense™ detects an electrical field that interacts with a T6 reference signal, showing a voltage value on the tester’s display.

Key features

  • Measure voltage to 1000 V AC without test leads
  • Simultaneously measure voltage and current
  • 17.8 mm open fork is widest in the industry
  • Measure up to 200 A on 4/0 wires (120 mm2)

Specifications: Fluke T6-1000 Electrical Tester

Measurement Specifications
Function Requires test leads Range Resolution Accuracy[1]
FieldSense
ac voltage true-rms
No 1000 V 1 V ± (3 % + 3 counts) 45 Hz - 66 Hz[2][3]
FieldSense
ac current true-rms
No 200.0 A 0.1 A ± (3% + 3 counts) 45 Hz - 66 Hz
FieldSense
frequency (Hz)
No 45 Hz – 66 Hz 1 Hz ± (1% + 2 counts)[3]
Volts ac true-rms Yes 1000 V 1 V ± (1.5% + 2 counts) 45 Hz - 66 Hz
Volts dc Yes 1000 V 1 V ± (1% + 2 counts)
Resistance Yes 2000 Ω 1 Ω ± (1% + 2 counts)
Yes 20.00 kΩ 0.01 kΩ
Yes 100.0 kΩ 0.1 kΩ
Safety   1000 V CAT III
600 V CAT IV
   

Accuracy[1]: ± ( [ % of reading] + [number of least significant digits] ). Accuracy is specified for 1 year after calibration, at 18 °C to 28 °C (64 °F to 82 °F) with relative humidity to 90 %. AC measurements are ac-coupled, RMS responding.
Accuracy[2]: Add 3 % without an external ground connection. External ground connection required for user wearing insulated gloves, standing on an insulated ladder, or otherwise insulated from earth ground.
Accuracy[3]: FieldSense is specified from 16 V to 100 % of range.

 
General Specifications
Calibration 1-year calibration cycle
Dimensions 61.1 x 259.3 x 43.8 mm
Jaw opening 17.8 mm
Weight 0.35 kg (0.78 lb)
Temperature Operating -10 °C to +50 °C (14 °F to 122 °F)
Storage -30 °C to +60 °C (-22 °F to +140 °F)
Altitude Operating 2,000 m (6,562 feet)
Storage 10,000 m (32,808 feet)
Relative Humidity 0% to 90%, 5 °C to 30 °C (41 °F to 86 °F)
0% to 75%, 30°C to 40 °C (86 °F to 104 °F)
0% to 45%, 40°C to 50 °C (104 °F to 122 °F)
Battery Type and Life 2 x AA (IEC LR6); 360 hours continuous, typical; 200 hours using FieldSense
Temperature coefficient 0.1 x (specified accuracy) / °C for <18°C or >28 °C
0.1 x (specified accuracy) / °C for <18°C or >28 °C
Safety IEC/EN 61010-1: Pollution Degree 2
Electromagnetic Environment IEC/EN 61326-1: Portable