Description
Product overview: Fluke T6-1000 Electrical Tester
Measure voltage without test leads
The Fluke T6-1000 Electrical Tester with FieldSenseâ„¢ technology lets you quickly, safely take True rms voltage and current measurements without test leads.
Unlike other fork testers that merely detect voltage, the T6-1000 makes actual measurements, without contacting a live, metallic conductor. Just slide the 17.8 mm open fork, the widest in the industry, over a conductor and read simultaneous voltage and current values. Or simultaneous frequency and current values. The open fork works with wires up to AWG 4/0 (120 mm2). Or, you can use the attached test leads to measure voltage DC to 1000 V.
- True rms voltage and current to 200 A AC, 1000 V AC
- Resistance 1 Ω to 100 kΩ
Work on any jobsite
Make use of the HOLD button to temporarily freeze the reading on the screen so you can keep working with the same measurement up. Plus, the display features large, easy-to-read numbers and a backlight for darker work environments or inside cabinets. The T6-1000 works with the Fluke TPACK ToolPakâ„¢ Magnetic Meter Hanger to make it even more convenient.
How FieldSenseâ„¢ technology works
FieldSense ™ technology is different than other open fork testers work by interpreting a magnetic field to show AC current. FieldSense™ detects an electrical field that interacts with a T6 reference signal, showing a voltage value on the tester’s display.
Key features
- Measure voltage to 1000 V AC without test leads
- Simultaneously measure voltage and current
- 17.8 mm open fork is widest in the industry
- Measure up to 200 A on 4/0 wires (120 mm2)
Specifications: Fluke T6-1000 Electrical Tester
Measurement Specifications | ||||
---|---|---|---|---|
Function | Requires test leads | Range | Resolution | Accuracy[1] |
FieldSense ac voltage true-rms |
No | 1000 V | 1 V | ± (3 % + 3 counts) 45 Hz - 66 Hz[2][3] |
FieldSense ac current true-rms |
No | 200.0 A | 0.1 A | ± (3% + 3 counts) 45 Hz - 66 Hz |
FieldSense frequency (Hz) |
No | 45 Hz – 66 Hz | 1 Hz | ± (1% + 2 counts)[3] |
Volts ac true-rms | Yes | 1000 V | 1 V | ± (1.5% + 2 counts) 45 Hz - 66 Hz |
Volts dc | Yes | 1000 V | 1 V | ± (1% + 2 counts) |
Resistance | Yes | 2000 Ω | 1 Ω | ± (1% + 2 counts) |
Yes | 20.00 kΩ | 0.01 kΩ | ||
Yes | 100.0 kΩ | 0.1 kΩ | ||
Safety | Â | 1000 V CAT III 600 V CAT IV |
 |  |
Accuracy[1]: ± ( [ % of reading] + [number of least significant digits] ). Accuracy is specified for 1 year after calibration, at 18 °C to 28 °C (64 °F to 82 °F) with relative humidity to 90 %. AC measurements are ac-coupled, RMS responding. |
General Specifications | ||
---|---|---|
Calibration | 1-year calibration cycle | |
Dimensions | 61.1 x 259.3 x 43.8 mm | |
Jaw opening | 17.8 mm | |
Weight | 0.35 kg (0.78 lb) | |
Temperature | Operating | -10 °C to +50 °C (14 °F to 122 °F) |
Storage | -30 °C to +60 °C (-22 °F to +140 °F) | |
Altitude | Operating | 2,000 m (6,562 feet) |
Storage | 10,000 m (32,808 feet) | |
Relative Humidity | 0% to 90%, 5 °C to 30 °C (41 °F to 86 °F) | |
0% to 75%, 30°C to 40 °C (86 °F to 104 °F) | ||
0% to 45%, 40°C to 50 °C (104 °F to 122 °F) | ||
Battery Type and Life | 2 x AA (IEC LR6); 360 hours continuous, typical; 200 hours using FieldSense | |
Temperature coefficient | 0.1 x (specified accuracy) / °C for <18°C or >28 °C | |
0.1 x (specified accuracy) / °C for <18°C or >28 °C | ||
Safety | IEC/EN 61010-1: Pollution Degree 2 | |
Electromagnetic Environment | IEC/EN 61326-1: Portable |